Limit the effects of combustible dust fires & explosions

A deflagration is a flame that spreads very quickly through dust suspended in the air. If a deflagration happens inside an enclosed or partially enclosed space, like equipment or a room, it can quickly build up dangerous air pressure. This can lead to an explosion. Even with the right controls in place, a fire or deflagration can still happen. You must be ready to suppress a fire, minimize the effects of a deflagration, and confirm it’s safe before you get back to work.

Be ready to suppress a fire

You must be able to suppress a fire involving your combustible dust. Work with a qualified person to select and install a suppression system that's adequate for your dust and your workplace.

Your system must:

  • Limit how much of the dust burns, so the fire doesn't spread further.
  • Limit the effects of the fire. This includes noticing whether it's the dust itself burning, or a substance created by a reaction involving the dust.

You must use the suppression system in a way that doesn't stir up settled dust and suspend it in the air.

Some dusts need special suppression methods. For example, some react dangerously with water. There are specific rules if you have metal dusts in your workplace.

Minimize the effects of a deflagration

You must be able to minimize the effects of a deflagration. Work with a qualified person to select and install a suitable way to do this.

Install relief vents

Venting is the most common way to limit the damage of a deflagration. There are two types of vents:

  • Passive vents, like open hatches, escape stacks, or flameless vents such as spring or rupture-type vents. These vents don’t need sensors. They give the rising pressure and flame a path to a safe location.
  • Active vents, like an abort gate. These are monitored by sensors that trigger a protective device when they detect a specific condition, like a sudden pressure increase.

If you use deflagration relief vents:

  • Work with a qualified person to design and locate them to minimize risk to workers and other people.
  • Design them so the vents don’t send any exhaust into occupied areas.
  • Mark the vents and their blast areas with signs that clearly identify the hazard.

Use containment spaces

If containment spaces are built to withstand the maximum pressure of a fire or explosion, this is considered a passive isolation method. It doesn’t need sensors, a response system, or relief vents.

Most dust handling systems aren’t built to withstand these pressures, so containment isn’t used on its own as often.

Install detection and alarm systems

These systems detect a deflagration early and act automatically to limit the damage. Sensors monitor for signs of a deflagration, such as a sudden pressure increase. They can respond within milliseconds to:

  • Close physical barriers, such as fast-acting slide gates
  • Release a chemical agent to isolate and extinguish the flame before it spreads

If your workplace has ducting or enclosed conveyors that move combustible dusts you should use a spark detection and extinguishing system. This:

  • Detects sparks before they can ignite dust
  • Triggers a response, such as injecting water, to put them out

These systems must be inspected, tested, and maintained regularly to make sure the sensors and response devices work when needed.

Confirm it's safe before restarting

You must develop written response procedures for combustible dust incidents to safely go back to work after a fire or deflagration.

Before restarting, make sure you:

  • Confirm the fire or deflagration is completely out.
  • Restore your risk controls to full working order.
  • Let affected workers know once you’ve done both of these things.

Please note: The content on this page is intended to help you understand and meet the requirements of the Occupational Health and Safety Regulation. More detailed information can be found in the OHS Guidelines and/or OHS Regulation.