Capture dusts with the right equipment
You must minimize how much combustible dust escapes from your machinery and equipment. This includes bulk storage in enclosures, like silos and bins, and elsewhere
If the escaping dust could catch fire or explode, you must capture it. If the dust is suspended in air, you must use a dust collection system to capture it, if possible.
You must work with a qualified person to design, select, or change your dust capture equipment.
Design your dust collection system
You must work with a qualified person, or under their supervision, whenever your dust collection system is:
- Designed
- Built
- Installed
- Changed
This applies even if you buy a system from a manufacturer and they install it.
Your system must meet the requirements of the:
- OHS Regulation
- BC Building Code
- BC Fire Code
- BC Electrical Code
The qualified person you are working with should also refer to the NFPA 660 standard.
Know the main parts of a dust collection system
Dust collection systems include these parts:
- Hoods: These capture dust at the source, before it can spread into the workplace.
- Ducts: These carry the dust-laden air from the hoods to the separator.
- Air-material separators (AMSs): These remove the dust from the air.
- Air-moving devices (AMDs): These use fans or blowers to move the air through the system.
- Active explosion suppression systems or passive isolation devices
Choose the right air-material separator
There are four main types of AMSs. Each works differently, and each has pros and cons, depending on your dust and your workplace:
- Fabric separators (baghouses): These pass dust-laden air through fabric filters that trap the dust.
- Wet separators: These use a liquid, usually water, to wash dust out of the air.
- Mechanical separators: These use physical force, such as a spinning cyclone, to separate dust from air.
- Electrostatic precipitators: These use an electric charge to pull dust out of the air. They’re useful if the air has already gone through another AMS, like a baghouse or a cyclone. They aren’t the right choice for air that has a high concentration of combustible dust.
Talk to your qualified person about which AMS best suits your:
- Dust
- Equipment
- Workplace
Consider a centralized vacuum for surface cleanup
A centralized vacuum system is a fixed set of pipes that uses suction from hose-connection stations to remove dust that has settled on surfaces, like:
- Floors
- Rafters
- Ledges
The system moves the dust to an AMS, usually located outside the building.
A centralized vacuum system shares many of the same design considerations as an AMS. These include grounding, bonding, and making sure hoses and pipes move air fast enough that dust doesn’t settle inside them.
Get approval before you recirculate exhaust air
You need approval from WorkSafeBC if you want to recirculate exhaust air back into your workplace.
Recirculating air can save on heating costs, but isn’t usually recommended for combustible dust because of fire and health hazards.
If you can provide enough filtration and deflagration protection, you may be approved to recirculate exhaust air. This will depend on the:
- Type of dust
- Activities in your workplace
- Design of the dust collection and recirculation system
Apply for WorkSafeBC approval before you purchase or install your air recirculation system. To get an acceptance, use the WorkSafeBC variance and acceptance process.
Dry dust collectors for metal dust are not approved for exhaust air recirculation.
The design of your recirculation system will depend on the design of the dust collection system and the control measures that you have in place. The following components are recommended for systems that recirculate exhaust air:
- A secondary AMS
- A bypass or backup route that can move exhaust to the outdoors
- Secondary filtration before the air re-enters the workplace (required)
- Devices that monitor how well the primary and secondary filters are working
- An automatic alarm that activates if the AMS malfunctions or becomes less effective
- An automatic shutdown feature triggered by fire or explosion
Know the restrictions for enclosureless air-material separators
An enclosureless air-material separator (EAMS) is an AMS that isn't confined within a closed space.
An EAMS typically recirculates filtered air back into the workplace. Because of this, there are restrictions on what kinds of combustible dust an EAMS can collect. You can’t use an EAMS if your workplace has dust from:
- Agricultural materials
- Metals
- Sulfur
EAMSs are common in small workplaces, like wood shops. That’s because they’re easy to install and only run while the connected machine is on.
Indoor installations are not recommended for EAMSs, although they are allowed in certain circumstances. Minimum clearance distances are listed below. For wood dusts, the clearance is based on the capacity of the EAMS:
- Capacity over 5,000 cubic feet per minute (cfm): Don’t install indoors.
- Capacity between 1,500 and 5,000 cfm: Keep at least 6.1 m (20 ft.) from:
- Emergency exit routes
- Worker areas
- Flammable materials
- Other separators
- Capacity under 1,500 cfm: Keep at least 3 m (10 ft.) from emergency exit routes. If you have more than one air-material separator, keep them at least 6.1 m (20 ft.) apart.
Design and balance your ducting
You must work with a qualified person to design ducting that will minimize combustible dust buildup. Some things to keep in mind:
- Use electrically conductive materials.
- Ground and bond the ducting to prevent a static charge from building up.
- Keep the air velocity in the main duct high enough that dust doesn’t settle inside.
- Avoid sharp bends and obstacles where you can, to reduce turbulence and pressure loss.
- Test and balance the system before you start using it, so airflow is right in every branch.
Balancing a dust collection system is a technical process that can affect airflow throughout the whole system.
Talk to a qualified person before making any changes. This includes disconnecting a branch line.
Work with your equipment suppliers and manufacturers
Suppliers and manufacturers of dust collection equipment have responsibilities under the Workers Compensation Act. They must:
- Give clear directions for using the equipment safely.
- Make sure the equipment is safe when used as directed.
- Make sure the equipment meets the requirements of the Act and the OHS Regulation.
Ask your supplier or manufacturer for written instructions on installing, operating, and maintaining your equipment safely.
Related information
- Variances to & acceptances under the OHS Regulation
- NFPA 660 Standard for Combustible Dusts and Particulate Solids
Please note: The content on this page is intended to help you understand and meet the requirements of the Occupational Health and Safety Regulation. More detailed information can be found in the OHS Guidelines and/or OHS Regulation.