Two workers injured when shoring cage in trench filled with soil

Date of incident: September 2024
Notice of incident number: 2024190550003
Employers: Construction company; engineering firm; equipment rental company

Incident summary
Workers were replacing underground sanitary infrastructure along a road. Two workers were inside a shoring cage (a support structure) within an excavation (trench) while an adjacent shoring cage was being lifted up by an excavator. Soil sloughed into the shoring cage the workers were in, burying the workers. Both workers sustained serious injuries.

 

Investigation conclusions

Cause

  • Shoring cage was below ground level and above bottom of trench. The shoring cage the workers were in was placed 1 m (3 ft.) below ground level and was not placed as close to the bottom of the trench as the material being installed would allow. The soil was able to slough over the top of the shoring cage because it was placed below ground level, and the shoring cage fell deeper into the trench when the adjacent cage was lifted because it was not placed on the bottom of the trench.
  • Workers in unsafe location during shoring cage movement. The two workers were inside the shoring cage while the adjacent shoring cage was being lifted, which resulted in the workers being buried by soil when it sloughed into the shoring cage.

Contributing factors

  • Poor soil condition. The width of the original trench (excavated 30 to 40 years before the incident) combined with poor soil compaction left by the installer of the original sanitary infrastructure increased the risk of soil sloughing into the trench.
  • Conflicting instructions provided to construction company. The written instructions contained in the excavation assessments provided by the engineering firm were inconsistent with the Occupational Health and Safety Regulation and with the tabulated data sheets (tables and charts signed off by a professional engineer) provided by the equipment rental company. The construction company followed the written instructions contained in the excavation assessments provided by the engineering firm, and in doing so placed the shoring cage 1 m (3 ft.) below ground level.
  • Unclear communication system. The communication system that was being used was vulnerable to misunderstandings and did not include call signs to identify who was speaking. As a result, the other workers were not sure where the two workers in the cage were located before the incident.

Other health and safety issues

  • No instructions for shoring cages used for access and egress. The engineering firm only provided written instructions in the excavation assessment for the shoring cages that workers would be working inside. However, the written instructions required by a professional engineer are not limited to working cages, and the requirements for safe use of a shoring cage apply equally to shoring cages within an excavation that are used for access and egress. It is not acceptable for workers to be exposed to unsafe excavation conditions and to the risk of soil sloughing into areas used for access and egress.
  • Excavation assessment not signed by professional engineer. The excavation assessment that was in place when the incident occurred was signed by a geoscientist, rather than a professional engineer, as required.

Request the full report

Publication Date: Nov 2026 Asset type: Incident Investigation Report Summary NI number: 2024190550003